Explain the importance of the air barrier of a house, how air sealing contributes to air tightness of a house, and the proper role of electric boxes that interact with the air barrier.

Correct Answer

verifed

verified

The air barrier of a house is one of the...

View Answer

A 3" x 2" 3 1/2" metal device box can hold a maximum of __________ 12 AWG conductors.


A) 10
B) 9
C) 8
D) 7

E) B) and C)
F) A) and B)

Correct Answer

verifed

verified

When computing box fill, all internal clamps count as ____________________ conductor(s) of the largest conductor in the box.

Correct Answer

verifed

verified

The actual volume for a 4" x 1 1/2" square box with a 21 cubic inch volume with a single gang 4" x 3/4" raised plaster ring with a marked volume of 4.5 cubic inches attached to it is:


A) 18 cubic inches
B) 21 cubic inches
C) 25.5 cubic inches
D) 30.5 cubic inches

E) A) and D)
F) None of the above

Correct Answer

verifed

verified

A device box or lighting outlet box can also be used as a junction box.

A) True
B) False

Correct Answer

verifed

verified

A metal 4" square box has ten 12 AWG conductors, four 12 AWG grounding conductors, and four external clamps. What is the minimum size 4" square box you could use?


A) 4 * 1 1/4
B) 4 * 1 1/2
C) 4 * 2 1/8
D) 4 11/16 * 1 1/4

E) A) and B)
F) A) and C)

Correct Answer

verifed

verified

When computing box fill, which of the following would count as one conductor?


A) Single-pole switch
B) External cable clamp
C) Duplex receptacle
D) None of the above

E) A) and D)
F) None of the above

Correct Answer

verifed

verified

D

In walls or ceilings made of noncombustible materials, electrical boxes must be mounted so they are __________ the finished wall surface.


A) set back no more than 1/8" from
B) set back no more than 1/4" from
C) set back no more than 1/2" from
D) flush with

E) A) and D)
F) A) and C)

Correct Answer

verifed

verified

When installing electrical boxes above a dropped ceiling, it is OK to have the boxes supported by the same wires that hold up the dropped ceiling.

A) True
B) False

Correct Answer

verifed

verified

The number of conductors permitted in a box is determined by __________.


A) the area of the box
B) the perimeter of the box
C) the volume of the box
D) Underwriters Laboratories

E) All of the above
F) C) and D)

Correct Answer

verifed

verified

When computing box fill, each 14 AWG lighting fixture wire counts as one conductor.

A) True
B) False

Correct Answer

verifed

verified

When computing box fill, 3 - 12 AWG conductors and 2 - 14 AWG conductors would total __________ cubic inches.


A) 10.00
B) 10.25
C) 10.50
D) 10.75

E) C) and D)
F) B) and C)

Correct Answer

verifed

verified

A ____________________ saw is used to cut holes in lath and plaster or sheetrock walls when installing old work electrical boxes.

Correct Answer

verifed

verified

keyhole

Nonmetallic device boxes used in residential wiring typically have both their cubic inch volume and the maximum number of 14, 12, and 10 AWG conductors marked on the box.

A) True
B) False

Correct Answer

verifed

verified

In residential wiring, which of the following is an area where Handy (Utility) boxes would not be used?


A) Unfinished basements
B) Unfinished garages
C) Outdoors
D) Storage buildings

E) B) and D)
F) None of the above

Correct Answer

verifed

verified

Each unspliced conductor that is less than 12 inches long running through a box is counted as ____________________ conductor when computing box fill.

Correct Answer

verifed

verified

The volume allowance for a 10 AWG conductor is ____________________ cubic inches.

Correct Answer

verifed

verified

2.50

The size of the opening of a standard metal device box used to mount a switch or receptacle in a wall is __________.


A) 2" * 4"
B) 2" * 2"
C) 4" * 4"
D) 3" * 2"

E) A) and D)
F) A) and C)

Correct Answer

verifed

verified

__________ have no ears on them and are designed to be attached directly to building framing members.


A) Old work boxes
B) New work boxes
C) Re-model boxes
D) Fill boxes

E) B) and C)
F) All of the above

Correct Answer

verifed

verified

For each looped or coiled, unbroken length of conductor at least 12 inches long which passes through a box without splice or connection, the volume allowance is __________ of the actual conductor size.


A) 1
B) 2
C) 3
D) not counted

E) B) and D)
F) B) and C)

Correct Answer

verifed

verified